| Model | LS-512 | LS-624 | LS-648 | LS-6110 | LS-6125 |
| Nominal Battery Voltage | 12 V | 24 V | 48 V | 110 V | 125 V |
| Continuous Power | 500 W | 600 W | 600 W | 600 W | 600 W |
| ½ Hour Rating | 550 W | 750 W | 750 W | 750 W | 750 W |
| Surge Rating (5 seconds) | 1500 W | 2000 W | 2000 W | 2000 W | 2000 W |
| Input Voltage Range | 10.5-17 V | 21-34 V | 42-68 V | 80-140 V | 96-160 V |
| Standby Current | 27 mA | 22mA | 19 mA | 16 mA | 15 mA |
| Inverter ON – no load | 0.42 A | 0.31 A | 0.18 A | 0.15 A | 0.14 A |
| Peak Efficiency | 90 % | 92 % | 93 % | 93 % | 93 % |
| Weight | 5.5 Kg | 5.5 Kg | 5.5 Kg | 4.7 Kg | 4.7 Kg |
| Dimensions | 260mm L x 160mm W x 100mm H | ||||
| Output Voltage | 230 V (+/- 4%) | ||||
| Output Waveform | True Sinewave | ||||
| Total Harmonic Distortion | < 4% | ||||
| Output Frequency | 50Hz (+/- 0.1%) | ||||
| Power Factor | All Conditions | ||||
| Opertating Temperatures | -10deg to +50deg | ||||
| Auto Start Sensitivity | 0 - 20 W adjustable | ||||
| Input/Output Isolation | 3500 V | ||||
| Protection Circuitry | Overtemperature - Overload/Short Circuit - Battery Undervoltage - Battery Overvoltage | ||||
| Battery Leads | 1.0m Long with 10mm Mounting Lug | ||||
| DC Isolation | Thermal/Magnetic Circuit Breaker | ||||
| Output Wiring | Single GPO | ||||
| Chassis | Powder Coated 2mm Aluminium | ||||
| Standards | AS2279, AS3000, AS3001, EN55014, & C-Tick | ||||
| Warranty | 2 Years Parts and Labour | ||||
| Ratings | Specifications @ 25°C Ambient, Nominal Battery Voltage & Unity Power Factor | ||||